TECHNICAL DATA: | |
Temperature control | self-optimizing, electronic microprocessor controller MP-888 with
digital display of the set and actual value. Automatic temperature monitoring. |
Flow control | electronically, with digital display and automatic control of the minimum flow. |
Cooling capacity Nominal |
28 kW - see diagram |
Temperature range Circulating water Air temperature |
+10°C up to +40°C +2°C up to +45°C |
Heating | 9 kW, manual switchable |
Content water tank | approx. 150 l |
Refrigerating agent | R-134a |
Pump capacity | max. 5 bar / max. 145 l/min - see pump diagram |
Compressor | hermetically sealed |
Condenser | air cooled, air inlet located on the rear, blow out located on the side/top |
Air volume | 5'700 m3/h (not relevant to WK) |
Power consumption | approx. 11.3 kW (heating mode approx. 11.3 kW, cooling mode approx. 6 kW) |
Connections To / from mould Automatic water refill Drain Cooling water inlet Cooling water outlet |
1" BSP female thread 3/8" BSP female thread 1/2 " BSP female thread 3/4" BSP female thread (only at WK) 1" BSP female thread (only at WK) |
Dimensions (L×W×H) | 1'100 × 790 × 1'660 mm, incl. castors |
Noise Level(in 3 m distance) | 68 dBA |
Weight | 330 kg empty |
Color | silvergrey RAL 7001 optional: stainless steel case, not varnished |